Ul 600V Type THW-2 Koperen Geleider Pvc Geïsoleerde Kabel
Haven: | Tianjin shanghai qingdao port |
Betalingsvoorwaarden: | L/C,D/P,T/T,Western Union |
Leveringscapaciteit: | 100000 Kilometer/kilometers per Month THW Kabel |
plaats van herkomst: | Hebei china |
naam van het merk: | Ren DA |
modelnummer: | THW TW THHW |
type: | Geïsoleerd |
toepassing: | Gebouw draad |
leidingmateriaal: | Koper |
dirigent type: | Effen of Streng |
isolatiemateriaal: | PVC |
Product naam: | THW DRAAD |
Certificering: | UL |
Dirigent: | Gestrande Koperen |
Standaard: | UL83 |
Nominale Spanning: | 600 V |
Isolatie: | PVC |
SIZE: | 14AWG 12AWG 10AWG 8AWG 6AWG 4AWG |
Kleur: | ROOD ZWART GEEL GROEN |
Markt: | Noord-amerika en zuid-amerika |
Details levering: | Binnen 15 dagen na ontvangst van uw storting |
Details verpakking: | Zachte verpakking of reel of standaard export drum |
Ul listed 600V Type THW-2 copper conductor pvc insulated cable
TOP TEN CABLE MANUFACTURER/EXPORTER IN CHINA
LARGEST CABLE MANUFACTUER IN NORTH CHINA
ANNUAL EXPORT VOLUME EXCEED 200MILLION USD
WITH UL,TUV,KEMA,CE,BV,PSB,SABS,LLOYD'S,GL,NK,KR,ABS PRODUCTS CERTIFICATIONS
WITH TUV TYPE TESTING REPORT
WIDE PRODUCTS RANGE
ISO9001,ISO18001,OHSAS18001 SYSTEM CERTIFICATIONS
CNAS APPROVAL LABROTARY
1 APPLICATION: General purpose wiring for lighting and power -residential,commercial, industrial buildings in accordance with the National Electrical Code, maximum conductor temperature of 75°C in wet or dry locations,for circuits not exceeding 600 volts
When used as type TW, conductor is suitable for use in wet or dry locations at temperatures rated 60°C.
When used as type THW, conductor is suitable for use in wet or dry locations at temperatures rated 75°C.
When used as type THW2, conductor is suitable for use in wet or dry locations at temperatures rated 95°C.
2 STANDARDS:
1. Listed by UL as Type THW per Standard 83.
2. All sizes carry the VW-1 flame test designation.
3. Listed by UL as Oil Resistant I.
4. Listed by UL as Sunlight Resistant (250 kcmil and larger, black only)
5. 250 kcmil and larger pass UL and IEEE-383 ribbon burner flame test and are listed For CT Use.
6. Conforms to Federal Specification J-C-30B.
7 Cable Construction
Conductor: Conductors shall be solid or Class B stranded annealed uncoated copper per UL Standard 83
Insulation:flame-retardant, moisture- and heat-resistant thermoplastic
insulation UL Standard 83.
3 Data sheet:
|
Insulation | Nom. | NEC | Approx. Wt. | ||
No. Of | lbs/1000ft | |||||
AWG or kcmil | Strands | Thickness | Diam. | Ampacity* | Copper | Net |
Mils | Inches | |||||
14 | Solid | 30 | 0.13 | 20 | 12 | 19 |
12 | Solid | 30 | 0.15 | 25 | 20 | 26 |
10 | Solid | 30 | 0.17 | 35 | 31 | 39 |
14 | 7 | 30 | 0.14 | 20 | 13 | 19 |
12 | 7 | 30 | 0.16 | 25 | 20 | 28 |
10 | 7 | 30 | 0.18 | 35 | 32 | 41 |
8 | 7 | 45 | 0.24 | 50 | 50 | 67 |
6 | 7 | 60 | 0.3 | 65 | 81 | 105 |
4 | 7 | 60 | 0.35 | 85 | 129 | 160 |
3 | 7 | 60 | 0.38 | 100 | 163 | 195 |
2 | 7 | 60 | 0.41 | 115 | 205 | 245 |
1 | 19 | 80 | 0.49 | 130 | 258 | 315 |
1/0 | 19 | 80 | 0.53 | 150 | 326 | 390 |
2/0 | 19 | 80 | 0.57 | 175 | 411 | 480 |
3/0 | 19 | 80 | 0.62 | 200 | 518 | 595 |
4/0 | 19 | 80 | 0.68 | 230 | 653 | 735 |
250 | 37 | 95 | 0.75 | 255 | 772 | 880 |
300 | 37 | 95 | 0.81 | 285 | 926 | 1040 |
350 | 37 | 95 | 0.86 | 310 | 1081 | 1205 |
400 | 37 | 95 | 0.9 | 335 | 1235 | 1365 |
500 | 37 | 95 | 0.98 | 380 | 1544 | 1685 |
600 | 61 | 110 | 1.09 | 420 | 1853 | 2030 |
750 | 61 | 110 | 1.19 | 475 | 2316 | 2510 |
1000 | 61 | 110 | 1.34 | 545 | 3088 | 3305 |
We are one of China top rank cable&wire manufacturer.Our products meet standards of GB, IEC DIN ASTM, JIS, NF, AS/NZS CSA GOST and so on. We also have obtained ISO9001,ISO14001,OHSAS18001, UL,CE,
KEMA, TUV, SABS,PBS,Bureau Veritas, Lloyd,GL,NK,KR certifications.
We have obtained UL certifications for TC cable, DLO cable,RHH/RHW/RHW-2,XHHW/XHHW-2/SIS, THHN,SER/SEU/USE, MV-90/MV-105,MC cable,AC cable,TECK 90,SOOW,Welding cable,Mining cable,type DG,PV cable,Shipboard cable and so on.
CNAS accredited national level laboratory.
(1).When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price,please call us or tell us in your e-mail so that we will regard your inquiry priority.
(2).How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight charge should be paid.
(3).How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7 days. The samples will be sent to you via express and arrive in 3~5 days.
(4).What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order.The best record we keep is delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months before the date you would like to get the products at your country.
- Next: 6.35/11KV SINGLE AL/XLPE/SWA/PVC TYPE A CABLES SANS1339
- Previous: 6.35/11KV SINGLE AL/XLPE/SWA/PVC TYPE A CABLES